S11 SERIES OIL TYPE TRANSFORMER

■ Rated power: 200-3150kVA, Voltage: 6kV(6.3kV, 6.6kV, 6.9kV)、10kV(10.5kV, 11kV)、20kV(20kV, 21kV, 22kV, 24kV).

■ The transformer is a transformer whose interior is isolated from the air surrounding, so the transformer oil can not absorb the outer moisture and the oxygen since the change of transformer's volume could be fixed with the flexibility of corrugated tank structure. Then the aging speed of insulated material will be decreased. Before running the machine, the work of core suspension checkup is not necessary. Clients could also be free from the later maintenance and reparation. The reliability of products is visibly upgraded. Products is designed with PCCAD, the characters are conformed to IEC 60076 and GB 1094, and passed qualification ISO 9001.

■ The coil is with high-intensity enameled wires (or paper wrapped wired). Bucket form or cake form, evenly coiled and installed. Its insulation structure is reasonable, and it has strong anti-shortcut capacity. All the screws will not become loose after long journey. All sealed parts use rubber, which could effectively anti-aging by heat, light and electricity, also emote controlled thermometer and pressure release valves which increase the reliability.

■ No devices like oil tank, and humidity absorber could assure the oil to be insulated from air and the oil could be used for 20 years consecutively without any treatment later.

■ High qualified rubber used for the sealing.
■ Oil filling in vacuum condition.

Application: Widely used in city network, petrochemical industry, metallurgy, textile, or the mines or companies where are under the condition of high humidity or with the difficulty in maintenance.

 

S11 series 6kv, 10kV transformer technical data

无标题文档
rated power (kVA) 200 250 315 400 500 630 800 1000 1250 1600 2000 2500
voltage(kV) 6, 6.3, 10, 10.5kV
HV tapping range(%) ±5, ±2*2.5
LV voltage(kV) 0.4
connection symbol Dyn11, Yyn0
no-load loss (W) 0.34 0.40 0.48 0.57 0.68 0.81 .0.98 1.15 1.36 1.64 1.94 2.30
load loss 75℃ (W) 2.73/2.60 3.20/3.05 3.85/3.65 4.52/4.30 5.41/5.15 6.20 7.50 10.30 12.00 14.50 18.30 21.20
no-load current(%) 1.0 0.9 0.9 0.8 0.8 0.6 0.6 0.6 0.5 0.5 0.4 0.4
short-circuit impedance(%) 4.0 4.0 4.0 4.0 4.0 4.5 4.5 4.5 4.5 4.5 5.0 5.0
SCB10 SERIES DRY TYPE TRANSFORMER

■ Rated power: 200-3150kVA, Voltage: 6kV(6.3kV, 6.6kV, 6.9kV), 10kV(10.5kV, 11kV), 20kV(20kV, 21kV, 22kV, 24kV).

■ High voltage coils are wrapped with Polyester enameled wires, filled with glass fiber, and then resin under vacuum condition. It becomes solid under high temperature. It is with high mechanical intensity, low discharge partly; Low voltage coils are wrapped with a whole piece of copper foil, with strong anti-shortcut capacity. The core is made of silicon steel. By reasonable choosing magnetic density, decrease the empty loading loss effectively.

■ Fire protection, anti-explosion, and no pollution.

■ Coil is free from humidity, low noise and capacity of heating dispersion.

■ Low loss, energy saving, free from maintenance, small volume, light, and easy for installation.

 

SCB10 series 10kV transformer technical data

无标题文档
rated power (kVA) 315 400 500 630 800 1000 1250 1600 2000 2500 3150
voltage 6, 6.3, 6.6, 10, 10.5, 11kV
rated insulation level 6 kV 时7.2kV – 10kV 时12kV
frequency 50Hz
Ambient Temp 40℃
Secondary no-load voltage 400V / 415V / 433V
HV tapping range ±2×2.5%
connection symbol Dyn11 or others
no-load loss (W) 840 940 1120 1240 1460 1700 2000 2360 2900 3420 4280
load loss 75℃ (W) 2950 3400 4160 5080 5930 6930 8260 9980 12310 14640 18860
load loss 120℃ (W) 3380 3890 4770 5820 6790 7940 9460 11430 14100 16760 21600
rated impedance voltage Uk (%) 4 4 4 6 6 6 6 6 6 6 7
no-load current (%) 0.7 0.6 0.6 0.5 0.5 0.5 0.5 0.5 0.5 0.4 0.4
noise level 1 m Lpa 48 48 48 48 49 49 49 49 50 50 50

SCB10 series 20kV transformer technical data

无标题文档
rated power (kVA) 315 400 500 630 800 1000 1250 1600 2000 2500 3150
voltage 15, 15.75, 16.5, 17.5, 20, 21, 22kV
rated insulation level 15 kV 时17.5kV –20kV 时24kV
frequency 50Hz
Ambient Temp 40℃
Secondary no-load voltage 400V / 415V / 433V
HV tapping range ±2×2.5%
connection symbol Dyn11 or others
no-load loss (W) 920 1090 1280 1460 1670 1970 2270 2650 3080 3680 4380
load loss 75℃ (W) 3460 4100 4910 5790 7000 8290 9770 11750 13880 16420 20480
load loss 120℃ (W) 3970 4700 5630 6630 8020 9490 11190 13460 15890 18790 23450
rated impedance voltage Uk (%) 6 6 6 6 6 6 6 6 6 6 7
no-load current (%) 0.7 0.6 0.6 0.5 0.5 0.5 0.5 0.5 0.5 0.4 0.4
noise level 1 m Lpa 48 48 48 48 49 49 49 49 50 50 50
明星案例
Estadio de la Copa Africana de Naciones 2009 Lubango, Angola
Estadio de la Copa Africana de Naciones 2009 Lubango, Angola
Serie y cantidad de grupos electrógenos: 4*BF-M1100S
2012 Centro de datos de Tianjin, China
2012 Centro de datos de Tianjin, China
Serie y cantidad: 6*BF-M1375
查看更多

CONTACT US

Add:No. 972, Antai 3rd Road, Xishan Eco & Tech Development Zone, Wuxi,Jiangsu , China. 214106

BAIFApower.com BAIFA© 2019 All Rights Reserved.  www.300.cn wuxi   苏ICP备19027668号-1    苏ICP备19027668号-2   Privacy Policy

ONLINE

Nombre de la aplicación del mensaje:
客户留言
Descripción:
验证码